VOLTAGE TESTER

KEW 1710

Discontinued Products

Replacement Products

Discontinued products

• Designed to meet international safety standards
IEC 61243-3/IEC 61010-1
Measurement Category (CAT) IV 600V
• Self-Diagnostic test
• AC and DC voltage tests up to 690V with LEDs and LCD
• Polarity indication
• Single-pole phase test
• Phase rotation test
• Double molding gives comfortable grip
• Continuity test
• Auto-power ON/OFF
• Pen light for illuminating measurement points
• Variable distance in socket, 16.7mm or 19.0mm
• Variable probe Tips, 1.6mm or 4mmφ
• Probe cover protects user and probe Tips
• IP65 (IEC 60529)

Product Overview

Voltage Test (Double-pole Test)

  • Connect both probes to the system under test.
  • The voltage is indicated by LEDs.
    Buzzer sounds and Live circuit LED lights up when a threshold voltage of 50V is exceeded.
  • Voltage polarity is indicated in following manner.

Single-pole Phase Test

  • Live circuit LED lights up and buzzer sounds when a voltage of approx. 100V AC or more exists in the object under test.

Distance Between Probes

  • Distance between probes is selectable, either 16.7mm or 19.0mm, by changing probes (L1 and L2) position manually.

Probe Protection Cover

4mm Tips Replacement

  • How to fixing 4mm Tips on L1 probe- and L2 probe+.

Specification

Voltage Test
Voltage Range 12 - 690V AC/DC
LED Nominal Voltage 12/24/50/120/230/400/690V
AC (45 - 400Hz), DC (±)
Tolerance
(Threshold Voltage)
Light on at more than:
7±3V (12V LED)
18±3V (24V LED)
37.5±4V (50V LED)
75%±5% of nominal voltage
(120/230/400/690V LED)
Response Time <0.5s at 100% of each nominal voltage
LCD Range/Resolution
(Auto-range)
300V (7.0 - 299.9V)/0.1V
690V (270 - 759)/1V
Accuracy (23±5ºC) ±1.5V (7 - 100V)
±1%±5dgt (100 - 690V)
AC (45 - 400Hz), DC(±)
Overrange Indication "OL"
Response Time <2s at 90% of each voltage
Peak Current ls<3.5mA (at 690V)
Measurement Duty 30s ON (operation time)
240s OFF (recovery time)
Internal Battery
Consumption
Approx. 33mA (battery 3V, measuring 690V AC)
Battery Life Approx. 2500 operations (30s ON/240s OFF duty)
Single-Pole Phase Test
Voltage Range 100 - 690V AC (45 - 100Hz)
180 - 690V AC (100 - 400Hz)
Phase Rotation Test
System Three-phase 4-wire system
200 - 690V phase-to-phase
(100 - 400V earth-to-phase)
AC 50/60Hz
Phase Range 120±5 degree
Continuity Test
Detection Range 0 - 400kΩ+50%
Test Current Approx. 1.5μA (battery 3V, 0Ω)
Internal Battery
Consumption
Approx. 30mA (battery 3V, 0Ω)
General
Operating temperature
and humidity ranges
-10 - 55ºC, max 85% RH
(no condensation)
Storage temperature
and humidity ranges
-20 - 60ºC, max 85% RH
(no condensation)
Applicable Standard IEC 61010-1 CAT III / IV 600V
IEC 61243-3 CAT II 690V
Pollution degree 2
IP Rating IP65 (IEC 60529)
Power Source LR03 1.5V×2 (3V)
Dimensions 241.5(L)×68.5(W)×28.5(D) mm
Weight 230g (including batteries)

Product category