AC/DC DIGITAL CLAMP METER

KEW 2009R

KEW 2009R
CE
• True RMS reading instrument ideal for accurate measurement of distorted waveforms and non-sinusoidal waveforms arising from thyristors
• Can measure AC and DC currents up to 2000A
• Output terminal for recorder connection
• Minimum resolution 0.1A
  • TRUE RMS
  • CAT4 600V
  • φ55
  • MAX2000A
  • DCACA
  • DCACV
  • Resistance
  • Continuitybuzzer
  • Frequency
  • DATAHOLD
  • PeakHold10ms
  • OutPut
  • AutoPowerOff
AC A 400.0/2000A
±1.3%rdg±3dgt (0 - 400.0A, 150 - 1700A) (45 - 66Hz)
±2.0%rdg±5dgt (0 - 400.0A, 150 - 1700A) (20Hz - 1kHz)
±2.3%rdg±3dgt (1701 - 2000A) (45 - 66Hz)
DC A 400.0/2000A±1.3%rdg±2dgt
AC V 40.00/400.0/750V
±1.0%rdg±3dgt (45 - 66Hz)
±1.5%rdg±5dgt (20Hz - 1kHz)
DC V 40.00/400.0/1000V±1.0%rdg±2dgt
Ω 400.0/4000Ω ±1.5%rdg±2dgt
(Electronic protection (no fuse) up to 600V)
Continuity buzzer Buzzer sounds below 20±1Ω
Hz 10.0 - 4000Hz±1.5%rdg±5dgt
(Input sensitivityCurrent: more than 40AVoltage: more than 10V)
Conductor size Ø55mm max.
Output Recorder :
DC400mV against AC/DC400.0A
DC200mV against AC/DC2000A
Applicable standards IEC 61010-1 CAT IV 600V / CAT III 1000V Pollution degree 2
IEC 61010-031, IEC 61010-2-032, IEC 61326-2-2
Power source R6 (1.5V) × 2
Dimension 250(L) × 105(W) × 49(D)mm
Weight Approx. 540g (including batteries)
Accessories 7107A (Test leads)
9094 (Carrying case)
R6 (AA) × 2, Instruction Manual
Optional Accessories 7256 (Output cord)

Accessories/Optional Accessories /Related Products