CLAMP POWER METER
Extremely large jaw with tear drop shape:
ideal solution for busbar and large currents!
- Current up to 1000A rms
- Voltage up to 1000V rms
- Harmonics up to 30th
- KEW 2060BT has a newly designed special jaw shape for using at a large busbar Extremely large jaw with tear drop shape can clamp a large busbar with safe
(Conductor size 75mm, Busbar 80mm x 30mm)
3D View
Video
Product Overview
1.Various measurement functions
- Measurements of current, voltage, power, harmonics and phase detection are possible.
- True RMS: Indicates a correct value at the distorted waveform.
- Functions of PEAK, MAX, MIN, AVG are available.
Easy to check the temporal change in the power source. - LCD can display simultaneously the values of voltage and frequency or power and power factor.
2.Power measurement
Power measurement on any wiring system is possible.
KEW 2060BT can perform Single-phase 2-Wire / Single-phase 3-Wire and balance and unbalance measurements of Three-phase 3-Wire / Three-phase 4 Wire. The double display can simultaneously show many parameters like W & PF, W & deg, W & VA, W & Var, V & A, etc.
Various parameters such as active/reactive/apparent power, power factor, phase differences (1P2W only) which are required for the power measurement can be measured. |
Total 3-phase power can be measured in simple steps. |
By setting the CT and VT ratio and measuring the secondary side of the transformation, the primary side value can be obtained. |
3.Harmonics measurement
Harmonics of the voltage and current, which cause various failures at the field, can be measured.
It is possible to measure and show each voltage and current harmonics up to 30th.
Total harmonics distortion factor is in two types of THD-R and THD-F. Each degree of harmonics can be shown on the LCD of the tester. Both the current value (or voltage value) and the content ratio can be displayed on the same screen.
4.Phase detection
5.Connectivity
- Dedicated Application "KEW Power*" supports both Android™ and iOS.
- LCD display can be checked at the smart devices.
- Measured values and graphs can be stored with a press of a button.
- Voltage and current can be shown in the waveform display. Existence of the harmonics can be found easy.
- Threshhold of each measured value can be set at the applicaion, and PASS and FAIL judgement is possible.
Specification
Wiring connections | 1P2W, 1P3W, 3P3W, 3P4W | ||||||
---|---|---|---|---|---|---|---|
Measurements and parameters |
Voltage, Current, Frequency, Active power, Reactive power, Apparent power, Power factor(cosθ), Phase angle, Harmonics(THD-R/THD-F), Phase rotation | ||||||
ACV | |||||||
Range | 1000V | ||||||
Accuracy | ±0.7%rdg±3dgt (40.0 - 70.0Hz) ±0.3%rdg±5dgt (70.1Hz - 1KHz) |
||||||
Crest factor | 1.7 or less | ||||||
ACA | |||||||
Range | 40.00/400.0/1000A (3 range auto) | ||||||
Accuracy | ±1.0%rdg±3dgt (40.0 - 70.0Hz) ±2.0%rdg±5dgt (70.1Hz - 1kHz) |
||||||
Crest factor | 3 or less on 40.00A/400.0A range, 3 or less 1500A peak on 1000A range | ||||||
Frequency | |||||||
Display Range | 40.0 - 999.9Hz | ||||||
Accuracy | ±0.3%rdg±3dgt | ||||||
Active power | |||||||
Range | 40.00/400.0/1000kW | ||||||
Accuracy | ±1.7%rdg±5dgt (PF1, sine wave, 45 - 65Hz) | ||||||
Apparent power | |||||||
Range | 40.00/400.0/1000kVA | ||||||
Accuracy | ±1dgt against each calculated value Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt |
||||||
Reactive power | |||||||
Range | 40.00/400.0/1000kVar | ||||||
Accuracy | ±1dgt against each calculated value Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt |
||||||
Power factor | |||||||
Display Range | -1.000 - 0.000 - +1.000 | ||||||
Accuracy | ±1dgt against each calculated value Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt |
||||||
Phase angle (1P2W only) | |||||||
Display Range | -180.0 - 0.0 - +179.9 | ||||||
Accuracy | Within ±3.0° | ||||||
Harmonics RMS(Content rate) | |||||||
Analysis order | 1st - 30th order | ||||||
Accuracy | ±5.0%rdg ± 10dgt (1 - 10th) ±10%rdg ± 10dgt (11 - 20th) ±20%rdg ± 10dgt (21 - 30th) |
||||||
Total harmonics THD-R/THD-F | |||||||
Display Range | 0.0% - 100.0% | ||||||
Accuracy | ±1dgt against the calculated results of each measured value | ||||||
Phase rotation | ACV 80 - 1100V (45 - 65Hz) | ||||||
Other functions | MAX/MIN/AVG/PEAK, Data hold, Bluetooth®, Backlight, Auto power off | ||||||
General | |||||||
Communication interface |
Bluetooth® 5.0 | ||||||
Power source | LR6 (AA) (1.5V) ×2 | ||||||
Continuous measuring time |
Approx. 58 hours | ||||||
Conductor size | φ75 mm max. (busbar of 80mm × 30mm) | ||||||
Dimension / Weight | 283(L) × 143(W) × 50(D) mm / Approx. 590g (including batteries) | ||||||
Applicable standards |
IEC 61010-1, IEC 61010-2-032, IEC 61326-1,2-2 ClassB |
||||||
Accessories | 7290 (Test leads) 9198 (Carrying Case) LR6(AA)×2, Instruction Manual |
* Some countries regulate the compliance with their Radio Law of the products equipped with BluetoothⓇ.
Please confirm it with your distributor before purchasing our products equipped with Bluetooth®.
Accessories
Catalog & Document
-
- Product Catalog
-
- KEW 2060BT Product Catalog (Vietnamese)(6.47 MB)
- KEW 2060BT Product Catalog (Thai)(6.51 MB)
- KEW 2060BT Product Catalog (Spanish)(6.24 MB)
- KEW 2060BT Product Catalog (Indonesian)(5.98 MB)
- KEW 2060BT Product Catalog (French)(6.12 MB)
- KEW 2060BT Product Catalog (Arabic)(6.29 MB)