MODEL 6020/6030|MULTI FUNCTION TESTER|PRODUCTS|KYORITSU

Font Size
Small
Medium
Large

MULTI FUNCTION TESTER

MODEL 6020/6030

Discontinued products
MODEL 6020/6030
AutoDischarge
Discontinued products
• Water resistant (IEC 60529 IP57)
• Test leads are stored in a cord reel module
• Easy-to-read large digital display
• The instrument automatically turns itself off in about 30 minutes to conserve battery life, if no push buttons are pressed.
• Illumination on test probes for work at night or in dimly lit locations
• Display back-light to improve legibility in poor lighting conditions
• Autoranging; three ranges for insulation resistance, two ranges for earth resistance and two AC voltage ranges
• The instrument and all accessories in one carrying case
• AC voltage range;
_True RMS sensing permits accurate measurement of voltage with distortion and harmonics generated by equipment using
SCRs or TRIACs.
• Insulation resistance range;
_ Three test voltages; Model 6020 (125V, 250V, 1000V)
_ Three test voltages; Model 6030 (250V, 500V, 1000V)
_ 1mA test current at the minimum load.
_ Automatically releases electric charges stored in the circuit under test.
_ Remaining charges can be observed on AC voltage range
_ Remote control switch on a test probe
• Earth resistance range;
_ Checks resistance of auxiliary earth bars
_ Can make both simplified and normal measurement
• Phase test;
_ LEDs indicate whether phase sequence is correct or reversed as well as open phase, if any.
_ Rated voltage from 100V to 600V AC
602060306020/30
Insulation Test Specifications
Test Voltage 125V/250V 250V/500V 1000V
Measuring Ranges
(MΩ)

0 - 1.999MΩ
1.00 - 19.99MΩ
10.0 - 199.9MΩ

0 - 19.99MΩ
10.0 - 199.9MΩ
100 - 1999MΩ
(3 auto ranges)
Accuracy ±2%rdg ±3dgt, ±10%rdg (on 1000 - 2000MΩ)
Open Circuit Voltage +20% -0% of Rated Test Voltage
Rated Test current 1mA DC +20%-0%
Short Circuit current 1.3mA DC approx.
Effect of AC Component
of Terminal Voltage
Within ±10% of reading when 5µF capacitor is connected in parallel on insulation test
Overload Protection 1200V (DC + ACp-p) for 10 seconds
Earth Resistance Test Specifications
Measuring Ranges(Ω) 0 - 199.9Ω
100 - 1999Ω (2 auto ranges)
Accuracy ±2%rdg ±3dgt
(at 500Ω auxiliary earth resistance)
Measuring Method By constant current inverter 820Hz approx. 2mA approx.
Overload Protection 200V AC for 10 seconds between measuring terminals
Voltage Test Specifications
Measuring Ranges (V) 0 - 199.9/100 - 600V (2 auto ranges)
Accuracy ±1%rdg ±4dgt
Sensing True RMS
Input Impedance 2MΩ
Overload Protection 900V AC for 1 minute
Phase Check Specifications
Measuring Range 100 - 600V (50Hz/60Hz)
(for checking correct or reverse phase and open phase)
General
Display 3 1/2(1999)digit large LCD
Response Time Approx. 4 seconds for AC voltage and earth resistance tests
Approx. 5 seconds for insulation resistance tests.
Withstand Voltage 5550V AC for one minute
Effect of Drop No electrical and mechanical damage shall occur when the unit
is dropped from a height of 1 m onto the concrete floor.
Effect of Temperature Readings shall not differ greater than specified below
when taken at a reference temperature of 23ºC and
varied temperature of 0ºC and 40ºC. AC Voltage 3% ±2 dgt
insulation resistance and earth resistance 5% ±2 dgt
Operating Temperature Range 0-40ºC
Dimensions 130 × 238 × 207mm
(main body plus cord reel module)
105 × 238 × 207mm (main body only)
Weight Approx. 1.6kg (main body only)
Approx. 750g (cord reel module only)
Power Supply 1.5V LR6 alkaline battery or equivalent × 8 (for main body only)
1.5V LR6 alkaline battery or equivalent × 1 (probe only)
Safety Standard IEC 61010-1 CAT III 600V Pollution Degree 2
Accessories 7092 (Cord Reel)
8082 (Extension Probe)
7089 (Test Lead (large))
7090 (Test Lead (small))
7088 (Test Lead for Phase Check)
7091 (Test Lead) x 1set(red-20m, yellow-10m, green-5m)
8083 (Auxiliary Earth Spikes) x 1set
9081 (Carrying Case)
LR6 x 9, Instruction Manual,
Shoulder strap, Shoulder Pad, Set of "0" rings
Optional 2417 (Water Proof Leakage Clamp Meter)
7093 (Cord for Extension Probe)
9080 (Aluminum Carrying Case)

*A full set (deluxe version complete with aluminum carrying case and leakage clamp meter) is available as Model 6020T or 6030T.

  • Inquiry by e-mail