MULTI FUNCTION INSTALLATION TESTER
Replacement Products
Discontinued products
LOOP+RCD
Product Overview
- Kew Combitester provides the ultimate in Microprocessor technology offering Loop and RCD tests with a comprehensive memory and downloading test results.
- LOOP Impedance 200/2000Ω range measurement is carried out using a test current of 15mA. This current will not trip RCD’s rated at 30mA or greater.
- High resolution for low Loop Impedance (resolution of 0.01Ω) on 20Ω range.
- Direct reading of Prospective Short Circuit Current (PSC) and earth fault current.
- RCD tests at 0 and 180 degree phase angle switch permit quick tests and consistent readings.
- Test of a large kind of RCD's Standard, Selective, AC and A (DC sensitive breakers).
- Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings.
- RCD Ramp test in order to indicate the actual tripping current of RCD.
- Contact Voltage Reading (UC). with two selectable contact voltage limits (50 and 25V).
- Visual indication of correct wiring status and automatic lock-out if test resistors overheats.
- Designed to IEC 61010-1, IEC 61557 and high protection degree IP54.
- The stored data can be transferred to PC via Optical Adapter Model 8212-RS232C and 8212-USB.
Specification
Loop Impedance Ranges (Z reading) |
20/200/2000Ω | |
---|---|---|
Loop Impedance Ranges without tripping RCDs |
200 and 2000Ω with 15mA of test current | |
Max test current on Loop ranges | 3A (20Ω) / 15mA (200 and 2000Ω) | |
PSC / Earth Fault Current Ranges | 200/2000A/20kA | |
RCD Test AC Type (Standard and Selective) |
× 1/2 | 10, 30, 100, 300, 500, 1000mA |
× 1 | 10, 30, 100, 300, 500, 1000mA | |
× 5 | 10, 30, 100mA | |
Auto Ramp | 10, 30, 100, 300, 500mA | |
RCD Test A Type (Standard and Selective) |
10, 30, 100, 300, 500mA | |
RCD Test Currents multipliers | × 1/2, × 1, × 5 (max 1000mA type AC) (max 500mA type A) |
|
RCD Test Time Duration | 1000ms: × 1/2, × 1, DC 200ms: × 5, DC (500mA), and × 1 (1000mA) |
|
RCD Ramp Test | From 20% to 110% of IΔn (AC type) | |
Contact Voltage Block (RCD) | 50V and 25V | |
Contact Voltage Reading (RCD) | 100.0V | |
Phase and Earth (2 wires only) measurements |
RCD (without DC) LOOP |
|
Working Voltage for Loop Tests | 20Ω: 230V+10%-15% 200/2000Ω: 230V+10%-15% and 400V+10%-15% |
|
Working Voltage for RCD Tests | 230V+10%-15% | |
Voltage Test | 100 - 260V [50Hz] (LOOP 200/2000Ω, PSC 200A:100 - 440V) |
|
Memory | 300 memory locations | |
PC Software, Connection Cable | optional with 8212-USB, 8212-RS232C | |
Safety Standards | IEC 61010-1 CAT III 300V, IEC 61557 |