Dielectric Absorption Ratio
DAR measurement is a diagnostic test similar to the Polarization Index (PI), but DAR takes the ratio of the Insulation Resistance usually measured at 30 sec and 1 min (other time settings are possible) instead of 1 min and 10 min typically of the PI.
DAR measurements are useful for instance when the PI is 2 or less even for new objects under test. In such cases, a min DAR value of 1.25 is required.
DAR | 1.4 or more | 1.25 - 1.0 | 1.0 or less |
---|---|---|---|
Criteria | Best | Good | Bad |