• Designed to meet international safety standard IEC 61010-1 CAT IV 600V.
• CAT IV Clamp Meters can measure the Voltage and Current in both every low and high power circuits.
• Thus, very useful for power distribution companies, power utilities and maintenance fields.
Specification
AC A | 0 - 600.0A ±1.5%rdg±5dgt (50/60Hz) ±3.5%rdg±8dgt (40 - 400Hz) |
---|---|
AC V | 6/60/600V Auto Ranging ±1.3%rdg±4dgt (50/60Hz) ±3.0%rdg±5dgt (40 - 400Hz) |
DC V | 600m/6/60/600V Auto Ranging ±1.0%rdg±3dgt |
Ω | 600/6k/60k/600k/6M/60MΩ (Auto Ranging) ±1%rdg±5dgt (600 - 6M) / ±5%rdg±8dgt (60M) |
Continuity buzzer | Buzzer Sounds at 100Ω |
Frequency/DUTY | 10/100/1k/10kHz (Auto Ranging) / 0.1 - 99.9% |
Conductor size | Ø33mm |
Applicable standards | IEC 61010-1 CAT IV 600V, IEC 61010-031, IEC 61010-2-032, IEC 61326 |
Power source | R03 (1.5V) (AAA) × 2 |
Dimension | 243(L) × 77(W) × 36(D)mm |
Weight | 300g |
Accessories | 7066A (Test leads) 9094 (Carrying case) Instruction Manual |
Catalog & Document
-