MULTI FUNCTION INSTALLATION TESTER
Discontinued products
• Water resistant (IEC 60529 IP57)
• Test leads are stored in a cord reel module
• Easy-to-read large digital display
• The instrument automatically turns itself off in about 30 minutes to conserve battery life, if no push buttons are pressed.
• Illumination on test probes for work at night or in dimly lit locations
• Display back-light to improve legibility in poor lighting conditions
• Autoranging; three ranges for insulation resistance, two ranges for earth resistance and two AC voltage ranges
• The instrument and all accessories in one carrying case
• AC voltage range;
_True RMS sensing permits accurate measurement of voltage with distortion and harmonics generated by equipment using
SCRs or TRIACs.
• Insulation resistance range;
_ Three test voltages; Model 6020 (125V, 250V, 1000V)
_ Three test voltages; Model 6030 (250V, 500V, 1000V)
_ 1mA test current at the minimum load.
_ Automatically releases electric charges stored in the circuit under test.
_ Remaining charges can be observed on AC voltage range
_ Remote control switch on a test probe
• Earth resistance range;
_ Checks resistance of auxiliary earth bars
_ Can make both simplified and normal measurement
• Phase test;
_ LEDs indicate whether phase sequence is correct or reversed as well as open phase, if any.
_ Rated voltage from 100V to 600V AC
Specification
6020 | 6030 | 6020/30 | |
---|---|---|---|
Insulation Test Specifications | |||
Test Voltage | 125V/250V | 250V/500V | 1000V |
Measuring Ranges (MΩ) |
0 - 1.999MΩ 1.00 - 19.99MΩ 10.0 - 199.9MΩ |
0 - 19.99MΩ 10.0 - 199.9MΩ 100 - 1999MΩ |
|
(3 auto ranges) | |||
Accuracy | ±2%rdg ±3dgt, ±10%rdg (on 1000 - 2000MΩ) | ||
Open Circuit Voltage | +20% -0% of Rated Test Voltage | ||
Rated Test current | 1mA DC +20%-0% | ||
Short Circuit current | 1.3mA DC approx. | ||
Effect of AC Component of Terminal Voltage |
Within ±10% of reading when 5µF capacitor is connected in parallel on insulation test | ||
Overload Protection | 1200V (DC + ACp-p) for 10 seconds | ||
Earth Resistance Test Specifications | |||
Measuring Ranges(Ω) | 0 - 199.9Ω 100 - 1999Ω (2 auto ranges) |
||
Accuracy | ±2%rdg ±3dgt (at 500Ω auxiliary earth resistance) |
||
Measuring Method | By constant current inverter 820Hz approx. 2mA approx. | ||
Overload Protection | 200V AC for 10 seconds between measuring terminals | ||
Voltage Test Specifications | |||
Measuring Ranges (V) | 0 - 199.9/100 - 600V (2 auto ranges) | ||
Accuracy | ±1%rdg ±4dgt | ||
Sensing | True RMS | ||
Input Impedance | 2MΩ | ||
Overload Protection | 900V AC for 1 minute | ||
Phase Check Specifications | |||
Measuring Range | 100 - 600V (50Hz/60Hz) (for checking correct or reverse phase and open phase) |
||
General | |||
Display | 3 1/2(1999)digit large LCD | ||
Response Time | Approx. 4 seconds for AC voltage and earth resistance tests Approx. 5 seconds for insulation resistance tests. |
||
Withstand Voltage | 5550V AC for one minute | ||
Effect of Drop | No electrical and mechanical damage shall occur when the unit is dropped from a height of 1 m onto the concrete floor. |
||
Effect of Temperature | Readings shall not differ greater than specified below when taken at a reference temperature of 23ºC and varied temperature of 0ºC and 40ºC. AC Voltage 3% ±2 dgt insulation resistance and earth resistance 5% ±2 dgt |
||
Operating Temperature Range | 0-40ºC | ||
Dimensions | 130 × 238 × 207mm (main body plus cord reel module) 105 × 238 × 207mm (main body only) |
||
Weight | Approx. 1.6kg (main body only) Approx. 750g (cord reel module only) |
||
Power Supply | 1.5V LR6 alkaline battery or equivalent × 8 (for main body only) 1.5V LR6 alkaline battery or equivalent × 1 (probe only) |
||
Safety Standard | IEC 61010-1 CAT III 600V Pollution Degree 2 | ||
Accessories | 7092 (Cord Reel) 8082 (Extension Probe) 7089 (Test Lead (large)) 7090 (Test Lead (small)) 7088 (Test Lead for Phase Check) 7091 (Test Lead) x 1set(red-20m, yellow-10m, green-5m) 8083 (Auxiliary Earth Spikes) x 1set 9081 (Carrying Case) LR6 x 9, Instruction Manual, Shoulder strap, Shoulder Pad, Set of "0" rings |
||
Optional | 2417 (Water Proof Leakage Clamp Meter) 7093 (Cord for Extension Probe) 9080 (Aluminum Carrying Case) |
*A full set (deluxe version complete with aluminum carrying case and leakage clamp meter) is available as Model 6020T or 6030T.