LOOP/PFC/PSC TESTER
Replacement Products
Discontinued products
• Custom microprocessor controlled for highest accuracy and reliability.
• 3 LEDs for checking correct wiring status.
• 15mA LOOP measurement:
LOOP impedance 2000Ω range measurement is carried out with low test current (15mA).
The current will not cause tripping out involved RCD even the one with the lowest nominal differential current (30mA).
• Safe voltage measurement function.
• Large custom digital display readout on all models.
• Measure low loop resistances(resolution of 0.01Ω)
• Automatic lock-out if test resister overheats.
• Large custom digital display readout .
• Visual indication of reversed phase and neutral wiring at socket.
• Designed to IP54 Rating
• Complies with IEC 61557
• Front Cover
Specification
Loop Impedance Ranges | 20/200/2000Ω |
---|---|
Loop Impedance Accuracy |
±2%rdg±4dgt |
AC Test Current | 20Ω 25A 200Ω 2.3A 2000Ω 15mA |
AC Test Period | 20Ω (20ms) 200Ω (40ms) 2000Ω (280ms) |
Voltage | 110V-260V ±2%rdg±4dgt |
Operating Voltage | 230V+10% -15% (195V - 253V) 50Hz |
Safety Standard | IEC 61010-1 CAT III 300V IEC 61557-1,-3 IEC 61010-2-031 Pollution Degree 2 |
IP Rating | IEC 60529-IP54 |
Dimensions | 185(L) × 167(W) × 89(D)mm |
Weight | 750g approx. |
Accessories | Molded plug test leads Pouch for test leads Shoulder Strap Instruction Manual |
Optional | 7121B (Simplified measurement probe) |
Catalog & Document
-
- Instruction Manual