HIGH VOLTAGE INSULATION TESTER
Test Voltage 12kV (max), Resistance 35TΩ (max)
- Test Voltage 12kV (max), Resistance 35TΩ (max)
- Short-Circuit Current 5mA (max)
- Graphic representation of the insulation resistance and leakage current versus time on large display with bar graph and backlight
- Print Screen Function enables to record up to 32 display screens
- Internal Memory can store about 43,000 data (max)
- Can be operated from internal rechargeable battery or from AC line
- Robust design for field use with IP64 rating (with lid closed)
Specification
Insulation resistance | ||||||
---|---|---|---|---|---|---|
Test voltage | 500V | 1000V | 2500V | 5000V | 10000V | 12000V |
Max measurement value | 500GΩ | 1TΩ | 2.5TΩ | 5TΩ | 35TΩ | |
Accuracy | 400kΩ to 50GΩ ±5%rdg±3dgt |
800kΩ to 100GΩ ±5%rdg±3dgt |
2MΩ to 250GΩ ±5%rdg±3dgt |
4MΩ to 500GΩ ±5%rdg±3dgt |
8MΩ to 1TΩ ±5%rdg±3dgt |
|
50.1 to 500GΩ ±20%rdg(*) |
101G to 1TΩ ±20%rdg |
251G to 2.5TΩ ±20%rdg |
501GΩ to 5TΩ ±20%rdg |
1.01 to 10TΩ ±20%rdg |
||
10.1 to 35TΩ | ||||||
Short circuit current | Max 5.0mA | |||||
Load resistor to output rated voltage | 0.5MΩ or more | 1MΩ or more | 2.5MΩ or more | 5MΩ or more | 20MΩ or more | 24MΩ or more |
Output voltage | ||||||
Rated voltage | 500V | 1000V | 2500V | 5000V | 10000V | 12000V |
Monitor accuracy |
±10%±20V | |||||
Output accuracy |
0 to +20% | 0 to +10% | -5 to +5% | |||
Selectable range |
50 to 600V (in steps of 5V) |
610 to 1200V (in steps of 10V) |
1225 to 3000V (in steps of 25V) |
3050 to 6000V (in steps of 50V) |
6100 to 10000V (in steps of 100V) |
10100 to 12000V (in steps of 100V) |
Voltage measurement | ||||||
Measuring range | DCV:±30 to ±600V ACV:30 to 600V (50/60Hz) |
|||||
Accuracy | ±2%rdg±3dgt | |||||
Current measurement | ||||||
Measuring range | 5.00nA to 2.40mA (Depending on the insulation resistance) |
|||||
Accuracy | ±5%rdg±5dgt | |||||
Capactince measurement | ||||||
Measuring range | 5.0nF to 50.0μF | 40.0nF to 1.00μF (Display range : 5.0nF to 60.0μF) |
||||
Accuracy | ±5%rdg±5dgt | |||||
General | ||||||
Applicable standards | IEC 61010-1 CAT IV 600V Pollution degree 2, IEC 61010-2-034, IEC 61010-031, IEC 61326, IEC 60529 (IP64): with the lid closed. |
|||||
Operating temperature and humidity range | -10ºC , Relative humidity 85% or less 50ºC /(when operating with an external power supply, no condensation) 0 to 40ºC /Relative humidity 85% or less (when operating with battery, no condensation) |
|||||
Storage temperature and humidity range | -20ºC to 60ºC / Relative humidity 75% or less (no condensation) | |||||
Power source |
Rechargeable Lead storage battery (12V)* Charging time: approx. 8 hours / AC Power supply (100V to 240V, 50/60Hz) * Continuous measuring time: Approx. 4 hours (a load of 100MΩ at the Insulation resistance 12000V Range.) Approx. 2 hours (Max current consumption in range while rated currents are maintained.) |
|||||
Dimension |
330 (L) × 410 (W) × 180 (D) mm *Instrument and Hard case | |||||
Weight |
Approx. 9kg (including battery) *Instrument and Hard case | |||||
Accessories |
7170 (Power cord[EU]) or 7240 (Power cord[UK]) 7224A (Earth cord) 7225A (Guard cord) 7226A (Line probe) 7227A (Line probe with alligator clip) 8029 (Extension prod) 8212-USB (USB adapter) Instruction manual |
|||||
Optional accessories |
7254 (Longer Line probe with alligator clip) |
Please download “KEW Windows for KEW 3128(software)” from here.
Optional Accessories
Catalog & Document
-
- Product Catalog
-
- Instruction Manual
-
- KEW 3128 Instruction Manual (Vietnamese)(5.68 MB)
- KEW 3128 Instruction Manual (Thai)(3.34 MB)
- KEW 3128 Instruction Manual (Spanish)(3.70 MB)
- KEW 3128 Instruction Manual (Indonesian)(3.57 MB)
- KEW 3128 Instruction Manual (French)(3.54 MB)
- KEW 3128 Instruction Manual (English)(5.49 MB)
- KEW 3128 Instruction Manual (Arabic)(3.70 MB)