Successfully identified the circuit giving leakage alarm and determined the root cause

Situation

[Japan]

A recorder we already owned was used to identify circuits with leakage current, but it was cumbersome to operate.

Solutions

Introduced CURRENT & VOLTAGE LOGGER KEW 5020

Customer Reviews

Leakage alarms occasionally occurred, so we installed the data logger KEW 5020 to investigate the circuits. As a result, we were able to identify the faulty circuit with the recorded leakage data.
The distribution board on the floor had 50 circuits. Using a large clamp sensor to record multiple circuits at once and gradually narrowed down the target circuit.
Although KEW 5020 has only three channels, it was very easy to set up.
After about two months, we successfully identified the circuit and determined the root cause.