All live conductors of electrical appliances and installations must be insulated to prevent electric shock hazards from inadvertent contact, fire hazards from short circuit and equipment damage. In addition, a low insulation resistance in installation will result in a leakage current, and hence causes a waste of energy which would increase the running costs of the installation.
Nominal circuit voltage(V) | Test voltage V DC | insulation resistance (Mohms) |
---|---|---|
SELV and functional extra-low voltage, when the circuit is supplied from a safety isolating transformer (SELV:Safety Extra-Low Voltage) |
250 | >0.25 |
Up to and including 500V with the exceptionof the above cases | 500 | >0.5 |
Above 500V | 1000 | >1.0 |
Minimum value of insulation resistance by IEC364-6-61 TABLE 61A
Insulation resistance must be checked by applying appliances or installations a higher voltage than its normal working voltage, because an insulation resistance is lower at higher voltage than at lower voltage. KYORITSU's insulation resistance testers provide measurement at high levels of test voltages.
Periodical test is also important to ensure that insulation of installations or appliances is not deteriorating. Foreign matter and mechanical factors like wear or breakage may reduce insulation resistance. Regular tests and data logs can detect possible fault in insulation.
A-Between live conductors
B-Between live conductors and earth
To give some of the examples;
Kyoritsu's dedicated leakage clamp meters Model 2412, 2413F, 2431, 2432, 2433, 2433R, and 2434 will be very helpful in identifying the possible causes of such accidents.