Loop Testing Methods

In the buildings mainly used for private residence where low voltage power is supplied from electric utilities the fundamental protection against electric shock hazards is provided by appropriately coordinating the function of an earthing circuit with automatic switches placed at the latter stage of indoor wiring circuits. This is intended to quickly cut off the supply to an earthing circuit where a fault occurs following touch voltage exceeding an acceptable limit. Proper protection against electric shock hazards is given when the TT wiring system satisfies the requirement as expressed by the following formula:
Ra × la < 50
where Ra is the sum of the resistances of earth bars and protective conductors and Ia is the maximum current of a protection system provided for installations, indicating that the value obtained by multiplying Ra with Ia is not more than 50V. This means a maximum voltage one can touch shall not exceed 50V in the event of an earth fault.

  • Method of earth fault loop impedance testing at socket outlet. As shown in Fig.1, total earth fault loop impedance can be measured by plugging a
    loop tester into socket . The value of earth fault loop impedance measured represents the sum of transformer coil winding resistance, phase conductor (L3) resistance and protective conductor (PE) resistance as well as source earth resistance and installation earth resistance. With the loop tester set to any one of the PSC (prospective short circuit current) range, it is also possible to measure earth fault current.


Fig.1
Earth fault loop impedance testing at socket outlet.