KYORITSU
HOME

PRODUCTS
   • Multimeters
   • Voltage Testers
   • Clamp Meters
   • Loggers
   • Insulation Testers
   • Earth Testers
   • LOOP/PFC/PSC
     Testers
   • RCD Testers
   • Multi Function Testers
   • Portable Appliance
     Testers
   • Power Meters
   • Sensors, Multi-Trans,
     Clamp Adaptors
   • Others
   • Accessories
   • Discontinued Products

 
Voltage Tester

KT 170
 
Instruction Manual
NEW
AC and DC voltage tests up to 690V with LED
Comply with the latest standards IEC 61243 and IEC 61010
Novel design
Large and bright LEDs: Values are visible in the dark place
Ergonomic design fits in the hand
Two functions are available in one model
"Measurement without battery" and "Self Test (all LED on)"
Test leads withstand harsh environments at low temperature
Penlight (white LED)
Auto-power ON/OFF
Audible indication
Variable test tips, φ2mm or φ4mm
Probe protection cover can store the attachment of caps
IP65 (IEC 60529)

KT 170
CE
Voltage Test (Double-pole Test) Single-pole Phase Test
Variable top tips Store the attachment of caps
Probe Protection Cover 4mm Tips Replacement
How to fixing 4mm Tips on L1 probe- and L2 probe+.
Voltage Test
Voltage Range 12 - 690V AC/DC
Nominal Voltage 12/24/50/120/230/400/690V
AC (16 - 400Hz), DC (±)
Tolerance
(Threshold Voltage)
Light on at more than:
7±3V (12V LED)
18±3V (24V LED)
37.5±4V (50V LED)
75%±5% of nominal voltage
(120/230/400/690V LED)
Response Time <0.6s at 100% of each nominal voltage
Peak Current ls<3.5mA (at 690V)
Measurement Duty 30s ON (operation time)
240s OFF (recovery time)
Single-pole Phase Test
Voltage Range 100 - 690V AC (50/60Hz)
Phase Rotation Test
System Three-phase 4-wire system
200 - 690V phase-to-phase AC (50/60Hz)
Phase Range 120±5 degree
Continuity Test
Detection Range 0 - 400kΩ+50%
Test Current Approx. 1.5μA (battery 3V, 0Ω)
General
Operating temperature and humidity ranges -15 - 55ºC, max 85% RH (No Condensation)
Storage temperature and humidity ranges -20 - 70ºC, max 85% RH (No Condensation)
Applicable Standards IEC 61243-3, IEC 61010-1, IEC 61010-031, IEC 61557-7
CAT Ⅲ 690V / CAT Ⅳ 600V Pollution degree 2
IP Rating IP65 (IEC 60529)
Power Source LR03 (AAA) 1.5V×2
Dimensions 246(L)×64(W)×26(D) mm
Weight 190g (including batteries)
Accessories LR03 (AAA) 1.5V×2, KTA01 (4mm metal tips [2pcs/set]),
KTA02 (4mm rubber caps [2pcs/set]), Instruction manual

PageTop

Copyright(c)2004 KYORITSU ELECTRICAL INSTRUMENTS WORKS, LTD. Sitemap | Contact Us | Terms of Use | Privacy Policy