Leakage & Load current clamp sensor |
 |
8147 |
| |
|
 |
| |
 * Cannot be used for power measurement.
|

|
|
 |
| |
| Conductor size |
Φ40 |
| Rated current |
AC 70A |
| Output voltage |
AC 3500mV/70A (AC 50mV/A) |
| Accuracy |
0~40A |±1.0%rdg±0.1mV (50/60Hz) |±2.0%rdg±0.2mV (40Hz~1kHz)
40~70A |±5.0%rdg (50/60Hz) |±10.0%rdg (45Hz~1kHz) |
| Withstand voltage |
AC 3540V for 5 seconds |
| Cable length |
Approx. 2m |
| Output connector |
MINI DIN 6pin |
| Operating temperature ranges |
0~50ºC, less than 85% RH (without condensation) |
| Output impedance |
Approx. 100Ω |
| Applicable standards |
IEC 61010-1:2001, IEC 61010-2-032:2002, CAT.III 300V pollution degree 2 |
| Dimensions |
128(L) x 81(W) x 36(D) mm |
| Weight |
Approx.240g |
| Accessories |
9095 (Portable case), Instruction manual, Cable marker |
| Option |
7146 (Banana Φ4 adjuster plug) 7185 (Extension Cable) |
|
|
|