Multi-Trans |
 |
8008 |
| |
|
| |
How
to Use
Clamp your instrument around the pick-up coil of the multi-tran.
Then, clamp the transformer jaws of the multi-tran on the conductor, as shown below.
Multiply the reading of your clamp meter by 10 to obtain the current value measured. |
|

 |
|
 |
| |
| Measuring Range |
0~3000A AC |
| Ratio/Range |
10 : 1 (input to output) |
| Accuracy |
|±2% of input±0.5A |
Allowable
Measurement Time |
0~1000A (continuous),
1000~1500A (10 minutes max.)
3000A
(30 seconds max.) |
| Conductor Size |
Ø100mm max.(100 × 150mm) |
| Frequency Response |
50Hz/60Hz |
| Safety Standard |
IEC61010-1 CAT.III 300V Pollution Degree 2 |
| Withstand Voltage |
3000V AC for 1 minute |
| Dimensions |
317(L) × 150(W) × 30(D)mm
45(L) × 40(W) × 10(D)mm Output coil |
| Weight |
750g approx. |
| Accessories |
9056(Carrying Case) |
For use with
following models * |
2002PA,
2002R, 2003A(AC
only), 2004(AC only), 2006,
2007A(AC only), 2009A(AC
only), 2608A, 2805, 2017,
2027,
2037(AC only),
2412, 2417, 8113(AC
only), 2031,
2033(AC only), 2431,
2432, 2433, 2433R,
2434 |
|
| * These Multi-Trans can not be used for leakage current measurement. |
|

| |