| Range |
Insulation resistance |
Voltage measurement |
| 500V |
1000V |
2500V |
5000V |
AC/DC V |
| Measuring range |
0.0~99.9MΩ 100~999MΩ |
0.0~99.9MΩ 100~999MΩ 1.00~1.99GΩ |
0.0~99.9MΩ 100~999MΩ 1.00~9.99GΩ 10.0~99.9GΩ |
0.0~99.9MΩ 100~999MΩ 1.00~9.99GΩ 10.0~99.9GΩ 100~1000GΩ (1TΩ) |
30~600V AC/DC [50/60Hz] |
| Accuracy |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt |±20%(100GΩ or more) |
|±2%rdg |±3dgt |
| Short Circuit Current |
1.3mA approx. |
------- |
| Rated test Current |
1mA to 1.2mA at 0.5MΩ load |
1mA to 1.2mA at 1MΩ load |
1mA to 1.2mA at 2.5MΩ load |
1mA to 1.2mA at 5MΩ load |
------- |
| Open circuit voltage |
500VDC
|
1000VDC
|
2500VDC
|
5000VDC
|
------- |
| Maximum display |
999 Counts (1000 counts only at 1000GΩ) |
630 Counts |
| Current consumption |
About 1000mA (During measurement) |
110mA approx. |
Withstand Voltage Safety standard |
5320V AC for 5 seconds IEC 61010-1 CAT.III 600V, pollution Degree 2 |
| Power supply |
DC12V : R14×8 |
| Dimensions |
205(L) × 152(W) × 94(D)mm |
| Weight |
1.8kg approx. |
| Accessories |
7165 (Line Probe) 7166 (Earth Cord) 7167 (Guard Cord) 8019 (Pickle Type Prod) 9124 (Hard Carrying Case) LR14×8pcs (Alkaline Battery Size) Instruction Manual |
| Optional |
8302 (Adaptor for recorder) 7168 (Line Probe) |