New Simplified Earth Tester |
 |
4300 |
| |
|
|
| |
| KEW 4300 is simplified earth resistance tester (based on 2-pole method) that can be used for various distribution lines and electrical appliances and it also can measure AC/DC voltage. (As for AC Voltages, true rms values can be obtained.) |
|
| • |
200/2000Ω (2 ranges): auto-ranging. |
| • |
Warning buzzer triggered at 100Ω or less. |
| • |
LED lights up when a large earth voltage is detected. |
| • |
Live circuit warning when 30V or higher voltage is detected. (KEW 4300 detects voltage even when measuring resistances.) |
| • |
LED light for illuminating measurement points. (It turns on/off automatically in relation to the ambient brightness.) |
| • |
Small test current (max 2mA) not triggering RCD. |
|

 |
|
 |
| |
|
| |
| Earth resistance ranges |
200.0/2000Ω (Auto ranging) ±3%rdg±5dgt |
| Voltage ranges |
AC: 5.0 ~ 300.0V (45 ~ 65Hz) ±1%rdg±4dgt DC: ±5.0 ~ 300.0V ±1%rdg±8dgt |
| Applicable standards |
IEC 61010-1 CAT.III 300V pollution degree 2 IEC 61010-031, 61557-1, -5 IEC 61326-1, 2-2, IEC 60529 (IP40) |
| Withstand voltage |
3540V AC for 5 seconds (between the electrical circuit and enclosure) |
| Power source |
Size AA alkaline battery × 2pcs |
| Dimensions |
232(L) × 51(W) × 42(D)mm |
| Weight |
220g approx. (including battery) |
| Accessories |
7248 (Test lead with Alligator clip and Flat test probe) 8072 (CAT.II Standard prod) 8253 (CAT.III Standard prod) 8017 (Extension prod long) 9161 (Carrying case) Instruction manual, LR6 (AA) × 2 |
|
|

|
|