 | Leakage Clamp Meters |
 |
2417  |
| |
|
| |
| • |
Water and dust proof construction. The instrument is protected against water and dust. |
| • |
True RMS for accurate measurement of non-sinusoidal waveform current. |
| • |
Selectable frequency response of 50/60Hz only or up to 1kHz. |
| • |
Automatically turns power off in about 30 minutes to conserve battery life. |
|

 |
|
 |
| |
AC A
(50/60Hz) |
200/2000mA/20/200/500A
(True RMS)
|±1.5%rdg±6dgt
(200/2000mA)
|±2%rdg±6dgt
(20/200A)
|±2.5%rdg±6dgt
(500A) |
AC A
(WIDE) |
200/2000mA/20/200/500A
(True RMS)
|±1%rdg±4dgt
[50/60Hz],
|±3%rdg±4dgt
[40Hz~1kHz] (200/2000mA)
|±1.5%rdg±4dgt
[50/60Hz],
|±3.5%rdg±4dgt
[40Hz~1kHz] (20/200A)
|±2%rdg±4dgt
[50/60Hz],
|±4%rdg±4dgt
[40Hz~1kHz] (500A) |
| Conductor Size |
Ø40mm max. |
| Safety Standard |
IEC 61010-1 CAT.III 300V IEC 61010-2-032 |
Effect of External
Stray Magnetic Field Ø15mm 100A |
10mA AC max. |
| Frequency Response |
40~400Hz |
| Withstand Voltage |
3700V AC for 1 minute |
| Power Source |
6F22 (9V) × 1 |
| Dimensions |
209(L) × 96(W) × 45(D)mm |
| Weight |
450g approx. |
| Accessories |
9079 (Carrying Case)
6F22 × 1
Instruction Manual |
| Optional |
8008 (Multi-Tran)* |
|
| * These Multi-Trans can not be used for leakage current measurement. |
|

| |